Sign In | Join Free | My bushorchimp.com
China Kingsine Electric Automation Co., Ltd. logo
Kingsine Electric Automation Co., Ltd.
Kingsine Electric Automation Co., Ltd. Specialize in Electric Power Testing
Verified Supplier

16 Years

Home > Protection Relay Testing >

Universal Protection Relay Testing complying IEC61850 SV & GOOSE

Kingsine Electric Automation Co., Ltd.
Trust Seal
Verified Supplier
Credit Check
Supplier Assessment

Universal Protection Relay Testing complying IEC61850 SV & GOOSE

Brand Name : KINGSINE

Model Number : K3163i

Certification : ISO9001, CE

Place of Origin : China

MOQ : 1 set

Payment Terms : T/T in advance, L/C

Supply Ability : 50 sets/month

Delivery Time : 15 working days

Contact Now

Universal Relay Test Set

All-in-one Complying IEC61850 SV & GOOSE

Product Advantage

◆ Digital signal complying IEC61850-9-1 / IEC61850-9-2 protocols.

◆ Synchronize with GPS,IRIG-B.

◆ Suitable testing for all kinds of electromagnetic relays,microcomputer relays.

Ordering Ref.

Model Current Outputs Voltage Outputs
K3166i 6×35A@450VA max / 3×70A@850VA max 7×310V@90VA max
K3163i 6×35A@450VA max / 3×70A@850VA max 4×310V@124VA max
K3130i 3×35A@450VA max 4×310V@124VA max

Features

All-in-one design,integrated IEC61850 SMV(Complied IEC61850-9-1,IEC61850-9-2,IEC61850-9-2LE) & GOOSE,6I+4V analog channels output,inbuilt GPS and IRIG-B,and other advanced functions.

1. Two 100Mbit Optical Fiber ports for SMV and GOOSE simulations(exchangeable with RJ45).

2. 6×35A & 4×310V independent high burden output channels.

3. 13 channels independent low-level signal outputs.

4. AC/DC measurement(8 channels inputs,class 0.05,0-600V/0-5A,auto range).

5. Transducer calibartion (class 0.02).

6. Energy meter calibration(Mechanical & Electronic meters).

7. Transient play back up to 3KHZ.

8. Light weight <18kg.

9.Fully function KRT software testing modules.

10.3-Years guarantee of free repair and life-long maintenance.

11.Free software upgrade.

Application

Testing Items ANSI® No.
IEC61850 numerical IEDs relay & merge unit --
Distance protection relay 21
Synchronising or synchronism-check relays 25
Undervoltage relays 27
Directional Power relays 32
Undercurrent or underpower relays 37
Negative sequence overcurrent relays 46
Overcurrent/ground fault relays 50
Inverse time overcurrent/ground fault relays 51
Power factor relays 55
Overvoltage relays 59
Voltage or current balance relays 60
Directional overcurrent relays 67
Directional ground fault relays 67N
DC overcurrent relays 76
Phase-angle measuring or out-of-step protection relays 78
Automatic reclosing devices 79
Frequency relays 81
Motor overload protection relays 86
Differential protection relays 87
Directional voltage relays 91
Voltage and power directional relays 92
Tripping relays 94
Voltage regulating relays --
Overimpedance relays, Z> --
Underimpedance relays, Z --
Time-delay relays --

K31 Series Characteristic

1. 10 Channels (6×35A & 4×310V) outputs, each output channels are independent and simultaneous

control of magnitude, phase angle and frequency values, able to inject DC, AC sine wave and up

to 20 × harmonics.

2. Variable battery simulator, DC 0-350V, 140Watts max.

3. 13 Low-level channels outputs up to 8Vac/10Vdc max.

4. 0-600V / 0-5A AC/DC measurement in 0.05 class.

5. Graphical test modules and templates for testing of various relays.

6. Quick relay testing facility in Manual mode.

7. Shot/Search/Check, Point & Click testing.

8. RIO/XRIO import & export facility.

9. Switch on to fault test(SOTF).

10.Power system model for dynamic testing.

11.Inbuilt GPS and IRIG-B sync end-to-end testing.

12.Online Vector display.

13.Automatic test results assume.

14.Automatic test report creation.

15.Anti-clipping detect,wrong wiring connect alarm and self-protect, overload and overheat protection.

Parameter

Voltage Outputs

Output Range & Power 4×310V ac (L-N) 124VA max each
2×620V ac (L-L) 248VA max each
3×350V dc (L-N) 140W max each
Accuracy AC:<0.03%Rd + 0.02Rg Typ. / <0.07%Rd + 0.03Rg Guar.
DC: ±10mV @<5V,±0.5% @ ≥5V
Resolution 1mV
Distortion <0.05% Typ. / <0.1% Guar.
Current Outputs
Output Range & Power 6×35A ac(L-N) 450VA max single
3×70A ac(2L-N) 850VA max single
1×100A ac(6L-N) 1200VA max
3×20A dc(L-N) 300W max each
Accuracy AC:<0.03%Rd + 0.02Rg Typ. / <0.15%Rd + 0.05Rg Guar.
DC: ±5mA @<1A,±0.5% @ ≥1A
Resolution 1mA
Distortion <0.05%Typ. / <0.1% Guar.

Low-Level Output

Quantity 13 Channels, 16 pin aviation socket
Voltage outputs range AC 0-8V, DC 0-10V
Current outputs range Nominal 2mA, 10mA max transient
Output Power ≥0.5VA
Accuracy (0.01~0.8 Vrms):<0.05% Typ. / <0.1% Guar.
(0.8~8 Vrms):<0.02% Typ. / <0.05% Guar.
Resolution 0.25mV
Distortion(THD%) <0.05%Typ. / <0.1% Guar.

Frequency & Phase Angle

Frequency Range DC~1KHZ, 3KHZ transient
Frequency Accuracy ±0.5ppm
Frequency Resolution 0.001Hz
Phase Range 0°~360°
Phase Accuracy <0.05°Typ. / <0.1° Guar. 50/60Hz
Phase Resolution 0.001°

IEC61850 Fiber & GOOSE Ethernet Ports (Optional Function)

Fiber Ports

2×100 Base-FX Full Duplex, LC type

(Optional to 10/100Mbit, Ethernet RJ45 type)

Fiber Type 62.5/125um (Multiple optical fiber, Orange Red)
Wavelength 1310nm
Transmit Distance >1Km
Indicator

Spd Green (light): Valid connection


Link/Act Yellow (Blinking): Data exchanging

Note: Hardware is ready, to be actived.

Aux. DC Voltage Source(Battery simulator)

Range 0~350V @ 180W max
Accuracy 0.5%Rg Guar.

Binary Input

Quantity 8 pairs
Type wet/dry, measurement
Threshold 10~600Vdc or potential free, Programmable
Time resolution 100us
Debounce time 0~25ms (Software Controlled)
Time range Infinite
Time errors ±1ms @ 0.001~1s, ±0.1% @>1s
Galvanic isolation 4 isolated with each 2 pairs

Binary Output (Relay Type)

Quantity 4pairs
Type Potential free relay contacts,software controlled
Break Capacity AC Vmax: 400Vac / Imax:8A / Pmax:2500VA
Break Capacity DC Vmax: 300Vdc / Imax:5A / Pmax:150W

Binary Output (Semiconductor Type)

Quantity 4pairs
Type Open-collector, 14 pin Aviation socket
Break Capacity DC

5~15Vdc / 5mA, 10mA max


AC not permit

Response time 100us

Synchronization

Synchronization Mode  GPS, SMA type antenna connector / IRIG-B / IEEE1588

Power supply & Environment

Nominal Input Voltage 100~240Vac
Permissible Input Voltage 85~264Vac, 125~350VDC
Nominal Frequency 50/60Hz
Permissible Frequency 45Hz~65Hz
Power Consumption 1500 VA max
Connection Type Standard AC socket 60320
Operating Temperature -10℃~55℃
Storage Temperature -20℃~70℃
Humidity <95%RH, non-condensing

Others

PC Connection RJ45 Ethernet, 10/100M
Grounding Terminal 4mm banana socket
Weight 18Kg
Dimensions(W×D×H) 468×375×164(mm)

Optional Modules

DC Measurement Input(Transducer calibrator) * Hardware is ready,to be actived.

Voltage input Range 0~±10V dc
Max Input ±11V dc
Accuracy <0.02% rg Typ. / <0.05% rg Guar.
Input Impedance 1M ohm
Current Input Range 0~±1mA / 1~20mA, auto range
Max Input 600mA
Accuracy <0.02% rg Typ. / <0.05% rg Guar.
Input Impedance 15 ohm

AC / DC Measurement Input( Standard meter ) * Require extra PCB installed in factory only

Input Quantity 8 channels (blend with binary input pairs)
Voltage rang 0~600Vrms (Rg: 0.1V,1V,10V,60V,600V)
Voltage accuracy <0.05% Rg
Current range Shunt input: 0~5Arms / 0~30Arms (Optional)
Current accuracy <0.1% Rg
Sample rate 10KHz
Input impedance 600KΩ
Frequency range 45~65Hz, Accuracy<0.01Hz
Phase accuracy 0~360°,<0.2° Typ.

Energy Meter Calibration * Hardware is ready,to be actived

Sensor Usage Mechanical meters / Electronic meters
Sensor Output High level : >4.5V, Low level: <0.2V
Pulse Input 1 pulse input port
Pulse Range 500KHz pulse input Max.
Pulse Output 1 Transistor output, Open-collector, 5-15Vdc/5mA


Product Tags:

protective relay tester

      

relay protection tester

      
Buy cheap Universal Protection Relay Testing complying IEC61850 SV &amp; GOOSE product

Universal Protection Relay Testing complying IEC61850 SV & GOOSE Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Kingsine Electric Automation Co., Ltd.
*Subject:
*Message:
Characters Remaining: (0/3000)